about Prestige Cable industries
Corporate Structure
Contact us
products
Approval
 
Constructional and other details Prestige 1100 volts Single Core Unarmoured/Armoured Cable
Nominal Conductor Area
mm2
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
Unarmoured AYY
Nom. Insulation thickness
Nom. Overall cable dia Approx. Weight
mm
mm
kg/km
1.20
12
180
1.20
13
220
1.40
15
280

1.40
16
370
1.60
18
470
1.60
20
580

1.80
22
700
2.00
24
840
2.20
27
1070

2.40
30
1290
2.60
34
1640

3.00
38
2060

3.40
42
2580

3.40
46
3150

3.40
51
3850
Armoured AYWaY
Nom. Insulation thickness
Nom. Overall cable dia Approx. Weight
mm
mm
kg/km
1.50
15
300

1.50
16
340
1.70
17
430

1.70
20
540

1.90
22
690

1.90
23
800
2.10
25
940

2.30
27
1100

2.50
31
1380

2.70
32
1650
3.00
38
2110
3.40
42
2600

3.90
47
3220
3.90
51
3840
3.90
56
4800
Current carrying capacity
-In ground
-In Air
amps amps.
86
84
100
105
120
130
140
155
175
190
195
220
220
250
240
290
270
335
295
380
325
435
345
480
390
550
440
640
490
720
Prestige 1100 volts Two Core Unarmoured/Armoured Cable
Nominal Conductor Area
mm2
16
25
35
50
70
95
120
150
185
240
300
400
Unarmoured AYY
Nom. Insulation thickness
Nom. Overall cable dia Approx. Weight
mm
mm
kg/km
1.00
19
410
1.20
20
410
1.20
21
490

1.40
24
640
1.40
27
800
1.60
31
1080

1.60
33
1240
1.80
36
1510
2.00
40
1840

2.20
44
2340
2.40
49
2890

2.60
55
3660

Armoured AYFY
Nom. Overall cable dia
Approx. Weight
mm
kg/km
21
820

22
700
23
810

26
990

29
1230

33
1560
34
1750

38
2060

41
2480

46
3040
51
3720
57
4520

Current carrying capacity
-In ground
-In Air
amps amps.
70
59
90
78
110
99
135
125
160
150
190
185
210
210
240
240
275
275
320
325
355
365
385
420
Prestige1100 volts Three Core Unarmoured/Armoured Cable
Nominal Conductor Area
mm2
16
25
35
50
70
95
120
150
185
240
300
400
Unarmoured AYY
Nom. Insulation thickness
Nom. Overall cable dia Approx. Weight
mm
mm
kg/km
1.00
20
370
1.20
21
540
1.20
23
650

1.40
26
830
1.40
29
1100
1.60
33
1410

1.60
35
1680
1.80
40
2080
2.00
43
2490

2.20
49
3260
2.40
53
3990

2.60
61
5150

Armoured AYFY
Nom. Overall cable dia
Approx. Weight
mm
kg/km
23
660

24
850
25
990

27
1260

30
1540

34
1910
36
2250

1
2730

44
3150

50
4030
54
4800
63
6030

Current carrying capacity
-In ground
-In Air
amps amps.
60
51
76
70
92
86
110
105
135
130
165
155
185
180
210
205
235
240
275
280
305
315
335
375
Prestige 1100 volts 3 1/2 Core Unarmoured/Armoured Cable
Nominal Conductor Area
mm2
25/16
35/16
50/25
70/35
95/50
120/70
50/70
185/95
240/120
300/150
400/185
Unarmoured AYY
Nom. Insulation thickness
Nom. Overall cable dia Approx. Weight
mm
mm
kg/km
1.2/1.0
23
630
1.2/1.0
24
730
1.4/1.2
28
830

1.4/1.2
31
1240
1.6/1.4
35
1620
1.6/1.4
38
2020

1.8/1.4
42
2340
2.0/1.6
46
2930
2.2/1.6
52
3750

2.4/1.8
59
4720
2.6/2.0
66
5900

Armoured AYFY
Nom. Overall cable dia
Approx. Weight
mm
kg/km
24
980

25
1140
29
1440

32
1720

36
2180

39
2600
44
3080

48
3680

53
4540

60
5600
67
6900
Current carrying capacity
-In ground
-In Air
amps amps.
76
70
92
86
110
105
135
130
165
155
185
180
210
205
235
240
275
280
305
315
335
375
Prestige 1100 volts Four Core Unarmoured/Armoured Cable
Nominal Conductor Area
mm2
16
25
35
50
70
95
120
150
185
240
300
400
Unarmoured AYY
Nom. Insulation thickness
Nom. Overall cable dia Approx. Weight
mm
mm
kg/km
1.0
20
480
1.2
24
540
1.2
26
830

1.4
30
1120
1.4
32
1400
1.6
38
1870

1.6
39
2190
1.8
43
2660
2.0
49
2490

2.2
55
4200
2.4
62
5320

2.6
71
6780

Armoured AYFY
Nom. Overall cable dia
Approx. Weight
mm
kg/km
21
780

25
1049
27
1240

31
1590

33
1880

39
2460
41
2830

44
3310

50
4030

56
5050
63
6220
72
7860

Current carrying capacity
-In ground
-In Air
amps amps.
60
51
76
70
92
86
110
105
135
130
165
155
185
180
210
205
235
240
275
280
305
315
335
375
Prestige 1100 volts Control Cable Unarmoured/Armoured Cable
Number of Cores
  2 3 4 5 6 7 10 12 14 19 24 30 37
Nominal Conductor Area 1.5 mm²
Nom. Insulation thickness
Nom. Overall cable dia Approx. Weight
mm
mm
kg/km
0.8
9
138
0.8
10
159
0.8
11
189
0.8
12
245
0.8
13
259
0.8
14
270
0.8
16
344
0.8
17
391
0.8
18
441
0.8
20
580
0.8
23
717
0.8
24
857
0.8
26
1022
Armoured YFY/YWY 1.5 MMČ
Nom. Overall cable dia
Approx. Weight
mm
kg/km
YWY
12
370
YWY
13
400
YWY
14
450
YWY
15
510
YWY
16
570
YWY
17
590
YWY
18
750
YFY
18
670
YFY
19
740
YFY
21
910
YFY
24
1100
YFY
25
1260

27
1460
Current carrying capacity
-In ground
-In Air
amps amps. 23
20
21
17
21
17
21
17
15
13
14
13
13
11
12
10
11
10
10
9
9
8
9
7
8
7
Prestige 1100 volts Control Cable Unarmoured/Armoured Cable Type:YY/YFY/YWY
Number of Cores
  2 3 4 5 6 7 10 12 14 19 24 30 37
Nominal Conductor Area 2.5 mm²
Nom. Insulation thickness
Nom. Overall cable dia Approx. Weight
mm
mm
kg/km
0.9
11
180
0.9
12
210
0.9
13
250
0.9
14
300
0.9
15
350
0.9
16
360
0.9
19
500
0.9
20
590
0.9
21
670
0.9
23
860
0.9
26
1060
0.9
28
1280
0.9
31
1580
Armoured YFY/YWY 2.5 MMČ
Nom. Overall cable dia
Approx. Weight
mm
kg/km
YWY
13
450
YWY
14
490
YWY
15
560
YWY
16
640
YWY
17
700
YWY
18
720
YWY
20
810
YFY
21
910
YFY
22
980
YFY
24
1220
YFY
28
1480
YFY
29
1760

32
2060
Current carrying capacity
-In ground
-In Air
amps amps. 32
27
27
24
27
24
27
24
22
18
20
17
18
15
17
14
16
13
14
12
13
11
12
10
11
9
Electrical Parameters Prestige 1100 volts Aluminium Conductor PVC insulated Power Cables to
Nominal Conductor Area mmČ 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000
D.C. resistance of Conductor
 At 20șC
-Single Core
-Multi Core
ohm/km
ohm/km
1.91
1.91
1.2
1.2
0.868
0.868
0.641
0.641
0.443
0.443
0.320
0.320
0.253
0.253
0.206
0.206
0.164
0.164
0.125
0.125
0.1000
0.100
0.0778
0.0778
0.0605
-
0.0469
-
0.0367
-
0.0291
-
Reactance of cable at 50Hz
 -Single Core
-Multi Core
ohm/km
ohm/km
0.124
0.0857
0.120
0.0846
0.115
0.0824
0.110
0.0819
0.104
0.0764
0.101
0.0763
0.0956
0.0747
0.0937
0.0748
0.0919
0.0732
0.0899
0.0726
0.0901
0.0724
0.0874
0.0716
0.0867
-
0.0861
-
0.0853
-
0.0835
-
Capacitance of cable
-Single Core
-Multi Core
Short Circuit rating of
Cable for 1 Sec.
ohm/km
ohm/km
kA
0.809
1.02
1.216
0.822
1.07
1.901
0.912
1.19
2.661
1.961
1.23
3.802
1.14
1.46
5.322
1.17
1.47
7.223
1.30
1.64
9.124
1.31
1.62
11.41
1.33
1.62
14.07
1.40
1.62
18.25
1.39
1.70
22.81
1.48
1.72
30.41
1.46
1.82
38.02
1.44
-
47.90
1.60
-
60.83
1.73
-
76.03
The current capacity or loading of cables & conductors is limited by the thermal, electrical and other associated losses provided by the conductor, insulation, protective covering and surroundings. Thus, the current carrying capacity of cable depends not only on size, type voltage grade, components, material design and manufacturing but also on a number of varied conditions of installation and use. It is desirable to determine the correct current carrying capacity on actual service conditions for each and every case. Any overloading of cables will reduce the life expectancy. At the Same time, under loading leads to uneconomic utilization of their capacity.

Standard conditions of installation:

1) Maximum conductor temperature
2) Thermal resistivity of soil
3) Thermal resistivity of PVC
4) Ambient air temperature
5) Ground temperature
6) Depth of laying (cable laid direct in ground)

-70șC
-150șC cm/watt
-650șC cm/watt
-40șC
-30șC
-75 cm for 1.1 kV &
90 cm for 3.3 kV

Note: For site conditions other than the above standard conditions of installation, the appropriate rating factors given must be used.

RATING FACTORS
Variation in ambient air temperature
Ambient temperatureșC
Rating factor
25
1.25
30
1.16
35
1.09
40
1.00
45
0.90
50
0.80
   
Variation in ambient air temperature
Ground temperatureșC
Approx. Weight
25
1.25
30
1.16
35
1.09
40
1.00
45
0.90
50
0.80
   
Variation in depth of laying in ground
Voltage
Grade
1.1kV

3.3kV
Depth
Upto 25 mm2
Above 25 & upto 300 mm2
Above 300 mm2
All Sizes
75
1.00
1.00
1.00
-
90
0.99
0.98
0.97
1.00
105
0.98
0.97
0.96
0.99
120
0.97
0.96
0.95
0.98
150
0.96
0.94
0.92
0.96
180 & above
0.95
0.93
0.91
0.95
   