| Constructional
and other details Prestige 1100 volts Single Core Unarmoured/Armoured
Cable
|
Nominal
Conductor Area |
mm2
|
25 |
35 |
50 |
70 |
95 |
120 |
150 |
185 |
240 |
300 |
400 |
500 |
630 |
800 |
1000 |
Unarmoured
AYY
Nom. Insulation thickness
Nom. Overall cable dia Approx. Weight |
mm
mm
kg/km |
|
1.20
13
220 |
1.40
15
280 |
1.40
16
370 |
1.60
18
470 |
1.60
20
580
|
1.80
22
700
|
2.00
24
840 |
2.20
27
1070
|
2.40
30
1290 |
2.60
34
1640 |
3.00
38
2060 |
3.40
42
2580 |
3.40
46
3150
|
3.40
51
3850 |
Armoured
AYWaY
Nom. Insulation thickness
Nom. Overall cable dia Approx. Weight |
mm
mm
kg/km |
1.50
15
300
|
1.50
16
340 |
1.70
17
430
|
1.70
20
540
|
1.90
22
690
|
1.90
23
800 |
2.10
25
940 |
2.30
27
1100 |
2.50
31
1380 |
2.70
32
1650 |
3.00
38
2110 |
3.40
42
2600 |
3.90
47
3220 |
3.90
51
3840 |
3.90
56
4800 |
Current
carrying capacity
-In ground
-In Air |
|
86
84 |
100
105 |
120
130 |
140
155 |
175
190 |
195
220 |
220
250 |
240
290 |
270
335 |
295
380 |
325
435 |
345
480 |
390
550 |
440
640 |
490
720 |
|
| Prestige
1100 volts Two Core Unarmoured/Armoured Cable |
| Nominal
Conductor Area |
mm2
|
16 |
25 |
35 |
50 |
70 |
95 |
120 |
150 |
185 |
240 |
300 |
400 |
Unarmoured
AYY
Nom. Insulation thickness
Nom. Overall cable dia Approx. Weight |
mm
mm
kg/km |
1.00
19
410 |
1.20
20
410 |
1.20
21
490 |
1.40
24
640 |
1.40
27
800 |
1.60
31
1080
|
1.60
33
1240
|
1.80
36
1510 |
2.00
40
1840
|
2.20
44
2340 |
2.40
49
2890 |
2.60
55
3660 |
Armoured
AYFY
Nom. Overall cable dia
Approx. Weight |
mm
kg/km |
21
820
|
22
700 |
23
810
|
26
990
|
29
1230
|
33
1560 |
34
1750 |
38
2060 |
41
2480 |
46
3040 |
51
3720 |
57
4520 |
Current
carrying capacity
-In ground
-In Air |
|
70
59 |
90
78 |
110
99 |
135
125 |
160
150 |
190
185 |
210
210 |
240
240 |
275
275 |
320
325 |
355
365 |
385
420 |
|
| Prestige1100
volts Three Core Unarmoured/Armoured Cable |
| Nominal
Conductor Area |
mm2
|
16 |
25 |
35 |
50 |
70 |
95 |
120 |
150 |
185 |
240 |
300 |
400 |
Unarmoured
AYY
Nom. Insulation thickness
Nom. Overall cable dia Approx. Weight |
mm
mm
kg/km |
1.00
20
370 |
1.20
21
540 |
1.20
23
650 |
1.40
26
830 |
1.40
29
1100 |
1.60
33
1410
|
1.60
35
1680
|
1.80
40
2080 |
2.00
43
2490
|
2.20
49
3260 |
2.40
53
3990 |
2.60
61
5150 |
Armoured
AYFY
Nom. Overall cable dia
Approx. Weight |
mm
kg/km |
23
660
|
24
850 |
25
990
|
27
1260
|
30
1540
|
34
1910 |
36
2250 |
1
2730 |
44
3150 |
50
4030 |
54
4800 |
63
6030 |
Current
carrying capacity
-In ground
-In Air |
|
60
51 |
76
70 |
92
86 |
110
105 |
135
130 |
165
155 |
185
180 |
210
205 |
235
240 |
275
280 |
305
315 |
335
375 |
|
| Prestige
1100 volts 3 1/2 Core Unarmoured/Armoured Cable |
| Nominal
Conductor Area |
mm2
|
25/16 |
35/16 |
50/25 |
70/35 |
95/50 |
120/70 |
50/70 |
185/95 |
240/120 |
300/150 |
400/185 |
Unarmoured
AYY
Nom. Insulation thickness
Nom. Overall cable dia Approx. Weight |
mm
mm
kg/km |
1.2/1.0
23
630 |
1.2/1.0
24
730 |
1.4/1.2
28
830 |
1.4/1.2
31
1240 |
1.6/1.4
35
1620 |
1.6/1.4
38
2020
|
1.8/1.4
42
2340
|
2.0/1.6
46
2930 |
2.2/1.6
52
3750
|
2.4/1.8
59
4720 |
2.6/2.0
66
5900 |
Armoured
AYFY
Nom. Overall cable dia
Approx. Weight |
mm
kg/km |
24
980
|
25
1140 |
29
1440
|
32
1720
|
36
2180
|
39
2600 |
44
3080 |
48
3680 |
53
4540 |
60
5600 |
67
6900 |
Current
carrying capacity
-In ground
-In Air |
|
76
70 |
92
86 |
110
105 |
135
130 |
165
155 |
185
180 |
210
205 |
235
240 |
275
280 |
305
315
|
335
375 |
|
| Prestige
1100 volts Four Core Unarmoured/Armoured Cable |
| Nominal
Conductor Area |
mm2
|
16 |
25 |
35 |
50 |
70 |
95 |
120 |
150 |
185 |
240 |
300 |
400 |
Unarmoured
AYY
Nom. Insulation thickness
Nom. Overall cable dia Approx. Weight |
mm
mm
kg/km |
1.0
20
480 |
1.2
24
540 |
1.2
26
830 |
1.4
30
1120 |
1.4
32
1400 |
1.6
38
1870
|
1.6
39
2190
|
1.8
43
2660 |
2.0
49
2490
|
2.2
55
4200 |
2.4
62
5320 |
2.6
71
6780 |
Armoured
AYFY
Nom. Overall cable dia
Approx. Weight |
mm
kg/km |
21
780
|
25
1049 |
27
1240
|
31
1590
|
33
1880
|
39
2460 |
41
2830 |
44
3310 |
50
4030 |
56
5050 |
63
6220 |
72
7860 |
Current
carrying capacity
-In ground
-In Air |
|
60
51 |
76
70 |
92
86 |
110
105 |
135
130 |
165
155 |
185
180 |
210
205 |
235
240 |
275
280 |
305
315 |
335
375 |
|
| Prestige
1100 volts Control Cable Unarmoured/Armoured Cable |
| Number
of Cores |
|
2 |
3 |
4 |
5 |
6 |
7 |
10 |
12 |
14 |
19 |
24 |
30 |
37 |
|
| Nominal
Conductor Area 1.5 mm² |
Nom.
Insulation thickness
Nom. Overall cable dia Approx.
Weight |
mm
mm
kg/km |
0.8
9
138 |
0.8
10
159 |
0.8
11
189 |
0.8
12
245 |
0.8
13
259 |
0.8
14
270 |
0.8
16
344 |
0.8
17
391 |
0.8
18
441 |
0.8
20
580 |
0.8
23
717 |
0.8
24
857 |
0.8
26
1022 |
Armoured
YFY/YWY 1.5 MMČ
Nom. Overall cable dia
Approx. Weight |
mm
kg/km |
YWY
12
370 |
YWY
13
400 |
YWY
14
450 |
YWY
15
510 |
YWY
16
570 |
YWY
17
590 |
YWY
18
750 |
YFY
18
670 |
YFY
19
740 |
YFY
21
910 |
YFY
24
1100 |
YFY
25
1260 |
27
1460 |
Current
carrying capacity
-In ground
-In Air |
amps
amps. |
23
20 |
21
17 |
21
17 |
21
17 |
15
13 |
14
13 |
13
11 |
12
10 |
11
10 |
10
9 |
9
8 |
9
7 |
8
7 |
|
|
| Prestige
1100 volts Control Cable Unarmoured/Armoured Cable Type:YY/YFY/YWY
|
| Number
of Cores |
|
2 |
3 |
4 |
5 |
6 |
7 |
10 |
12 |
14 |
19 |
24 |
30 |
37 |
|
| Nominal
Conductor Area 2.5 mm² |
Nom.
Insulation thickness
Nom. Overall cable dia Approx.
Weight |
mm
mm
kg/km |
0.9
11
180 |
0.9
12
210 |
0.9
13
250 |
0.9
14
300 |
0.9
15
350 |
0.9
16
360 |
0.9
19
500 |
0.9
20
590 |
0.9
21
670 |
0.9
23
860 |
0.9
26
1060 |
0.9
28
1280 |
0.9
31
1580 |
Armoured
YFY/YWY 2.5 MMČ
Nom. Overall cable dia
Approx. Weight |
mm
kg/km |
YWY
13
450 |
YWY
14
490 |
YWY
15
560 |
YWY
16
640 |
YWY
17
700 |
YWY
18
720 |
YWY
20
810 |
YFY
21
910 |
YFY
22
980 |
YFY
24
1220 |
YFY
28
1480 |
YFY
29
1760 |
32
2060 |
Current
carrying capacity
-In ground
-In Air |
amps
amps. |
32
27 |
27
24 |
27
24 |
27
24 |
22
18 |
20
17 |
18
15 |
17
14 |
16
13 |
14
12 |
13
11 |
12
10 |
11
9 |
|
|
| Electrical
Parameters Prestige 1100 volts Aluminium Conductor PVC insulated
Power Cables to |
| Nominal
Conductor Area |
mmČ |
16 |
25 |
35 |
50 |
70 |
95 |
120 |
150 |
185 |
240 |
300 |
400 |
500 |
630 |
800 |
1000 |
|
| D.C.
resistance of Conductor |
At
20șC
-Single Core
-Multi Core |
ohm/km
ohm/km |
1.91
1.91 |
1.2
1.2 |
0.868
0.868 |
0.641
0.641 |
0.443
0.443 |
0.320
0.320 |
0.253
0.253 |
0.206
0.206 |
0.164
0.164 |
0.125
0.125 |
0.1000
0.100 |
0.0778
0.0778 |
0.0605
- |
0.0469
- |
0.0367
- |
0.0291
- |
|
| Reactance
of cable at 50Hz |
-Single
Core
-Multi Core |
ohm/km
ohm/km |
0.124
0.0857 |
0.120
0.0846 |
0.115
0.0824 |
0.110
0.0819 |
0.104
0.0764 |
0.101
0.0763 |
0.0956
0.0747 |
0.0937
0.0748 |
0.0919
0.0732 |
0.0899
0.0726 |
0.0901
0.0724 |
0.0874
0.0716 |
0.0867
- |
0.0861
- |
0.0853
- |
0.0835
- |
|
| Capacitance
of cable |
-Single
Core
-Multi Core
Short Circuit rating of
Cable for 1 Sec. |
ohm/km
ohm/km
kA |
0.809
1.02
1.216 |
0.822
1.07
1.901 |
0.912
1.19
2.661 |
1.961
1.23
3.802 |
1.14
1.46
5.322 |
1.17
1.47
7.223 |
1.30
1.64
9.124 |
1.31
1.62
11.41 |
1.33
1.62
14.07 |
1.40
1.62
18.25 |
1.39
1.70
22.81 |
1.48
1.72
30.41 |
1.46
1.82
38.02 |
1.44
-
47.90 |
1.60
-
60.83 |
1.73
-
76.03 |
|
|
| The current capacity or loading of cables & conductors is limited
by the thermal, electrical and other associated losses provided
by the conductor, insulation, protective covering and surroundings.
Thus, the current carrying capacity of cable depends not only
on size, type voltage grade, components, material design and
manufacturing but also on a number of varied conditions of
installation and use. It is desirable to determine the correct
current carrying capacity on actual service conditions for
each and every case. Any overloading of cables will reduce
the life expectancy. At the Same time, under loading leads
to uneconomic utilization of their capacity. |
| Standard conditions of installation: |
1) Maximum conductor temperature
2) Thermal resistivity of soil
3) Thermal resistivity of PVC
4) Ambient air temperature
5) Ground temperature
6) Depth of laying (cable laid direct in ground) |
-70șC
-150șC cm/watt
-650șC cm/watt
-40șC
-30șC
-75 cm for 1.1 kV &
90 cm for 3.3 kV |
|
| Note: For site conditions other than the above
standard conditions of installation, the appropriate rating
factors given must be used. |
|
| RATING
FACTORS |
| Variation
in ambient air temperature |
Ambient
temperatureșC
Rating factor |
25
1.25 |
30
1.16 |
35
1.09 |
40
1.00 |
45
0.90 |
50
0.80 |
|
|
|
| Variation
in ambient air temperature |
Ground
temperatureșC
Approx. Weight |
25
1.25 |
30
1.16 |
35
1.09 |
40
1.00 |
45
0.90 |
50
0.80 |
|
|
|
| Variation
in depth of laying in ground |
Voltage
Grade
1.1kV
3.3kV |
Depth
Upto
25 mm2
Above 25 & upto 300 mm2
Above 300 mm2
All Sizes |
75
1.00
1.00
1.00
- |
90
0.99
0.98
0.97
1.00 |
105
0.98
0.97
0.96
0.99 |
120
0.97
0.96
0.95
0.98 |
150
0.96
0.94
0.92
0.96 |
180
& above
0.95
0.93
0.91
0.95 |
|
|
|
|
|